Overview Isolation HART intelligent temperature transmitter (round card) is used for thermal resistance (RTD), thermocou
SHARE

Description

Basic Info
Model NO. BT-1A
Certification CE
Customized Customized
Output Signal Hart
Working Temperature -40-80ºC
Supply Voltage DC12-40V
Stored Temperature -40-100ºC
Input Signal Thermal Resistance (Rtd), Thermocouple (Tc)
Specification 0.15kg
Trademark XYT
Origin Shaanxi
Production Capacity 50000/Year
Product Description

Overview
Isolation HART intelligent temperature transmitter (round card) is used for thermal resistance (RTD), thermocouple (TC) signal input, two-wire system 4 ~ 20mA analog output, It is configured by HART protocol and installed inside the sensor (Form B).

Specification

Enter
input signalThermal resistance (RTD), thermocouple (TC)
Cold junction compensation range-20~60ºC
Compensation accuracy±1 ºC
Output
output signal4~20mA, Superimposed HART agreement
Load ResistanceRL≤(Ue-12)/0.021
Upper and Lower limit overflowalarm output currentIH=21mA,IL=3.8mA
Power supply
Supply voltageDC12~40V
Other parameters
Temperature drift0.0075%FS/ºC
Response timeThe 700ms reached 90% of the final value
Working temperature-40~80ºC
Stored temperature-40~100ºC
Shock resistance4g/2~150Hz
installation angleUnlimited
Installation areab-type top box mounting
ElectromagneticMeet the requirements of gb / t18268 industrial equipment
DetialsDimension
Input type and transmission accuracy
ModelTypesMeasuringMinimumMeasuringConversion

RTD
Pt100-200.0~850.0ºC20ºC≤100ºC0.2%
>100ºC0.1%
Cu50-50.0~150.0ºC20ºC≤100ºC0.2%
>100ºC0.1%

 


TC
B400~1800ºC500ºC≤300ºC0.2%
>300ºC0.1%
E-100~1000ºC50ºC≤300ºC0.2%
>300ºC0.1%
J-100~1200ºC50ºC≤300ºC0.2%
>300ºC0.1%
K-180~1372ºC50ºC≤300ºC0.2%
>300ºC0.1%
N-180~1300ºC50ºC≤500ºC0.2%
>500ºC0.1%
R-50~1768ºC500ºC≤500ºC0.2%
>500ºC0.1%
S-50~1768ºC500ºC≤500ºC0.2%
>500ºC0.1%
T-200~400ºC50ºC≤500ºC0.2%
>500ºC0.1%
Note:The above accuracy data is obtained by testing under the environment temperature of 20 ºC± 2 ºC.The output accuracy "%" is relative to the set range. 3.The cold junction compensation error needs to be added when measuring thethermocouple.

WiringConfiguration diagram

4~20mA and Hart Output Temperature Transmitter B E J K N R S T Type Tc and Rtd General Type Temperature Transmitter

Installation DiagramCompany Profile
FAQ

1. How long will you reply me?Normally in 1 hours, no more than 12 hours.2. How can I get the quotation?Please provide specification and application including sensing element, pressure range, thread connection, pressure type, medium, electronic connection, shell material etc. More details, more accurate quotation and earlier response.3. Can I get sample?Contact with our staff online directly and they would check stock for you.4. Can I visit your factory?You are warmly welcomed, our factory is located at Baoji city, Shaanxi province, China.5. Can we use our logo on the products?Yes, we provide OEM/ODM service.6. How long is your warranty period?Warranty period from the date of acceptance of 12 months.7. What is your terms of payment?We could accept T/T, L/C, Western union, PayPal, credit Assurance.